← Energio SensorsDownload PDF
Application design guideES-DG-03Rev B · November 2026

Warehouses & high bay

Aisle-by-aisle occupancy control for storage, manufacturing and gyms

Design guide
Warehouses & high bay
Photo: Krisana Nakajo / Unsplash

Most warehouse aisles sit empty most of the day, which makes them the biggest energy win in the building. Every solution below controls each aisle on its own: the lights sit low or off until a lift turns in, come up to full, and drop back when the aisle empties.

Design goals

Solutions in this guide

Code checklist

RequirementTypical code targetHow the solutions meet it
Aisle controlEach aisle controlled independently of other aisles and open areasOne sensor group per aisle
Partial-offReduce lighting by at least 50% within 20 min of the aisle emptying0-10V dimming to the unoccupied level; time-out 20 min or less
Automatic shutoffBuilding-wide off when unoccupied (schedule or sensor)Sensors dim or turn off each aisle; add a schedule for after hours
Open areasSeparate control from aislesSeparate sensors over staging and dock areas

Typical requirements of ASHRAE 90.1-2019 and the 2021 IECC. Local amendments and other code editions differ; the adopted code for the project governs.

A

Solution A: High bay sensors over each aisle

Wired 0-10V · up to 46 ft
Aisle 1Aisle 2Aisle 3
  • High bay sensor and aisle pattern
  • Racking
  • Aisle (own control group)

DANLERS ISI-HBWD wide-detection sensors mount over the aisle centerline and dim that aisle's fixtures over 0-10V. Racking blocks the view, so each sensor sees only its own aisle.

  • Mount over the aisle centerline, about every 30 ft
  • Put the first and last sensor near the aisle ends
  • Wire each aisle's sensors in parallel to that aisle's drivers
QtyModelDescription
9ISI-HBWD10V12VHigh bay sensor, 0-10V, three per aisle
—12 V DC Class 2 supplySensor power per wiring guide
—0-10V control wiringOne group per aisle

Tech sheet: ES-TS-104

B

Solution B: Battery-free high bay sensors

Wireless · no control wiring
Aisle 1Aisle 2Aisle 3CCC
  • High bay sensor and aisle pattern
  • CAisle controller
  • Racking
  • Aisle (own control group)

ILLUMRA E9T-OSH self-powered high bay sensors link to an E9X-DUV-10VTP dimming controller for each aisle's circuit, so no low-voltage wiring runs across the racks.

  • Mount E9T-OSH at 15–40 ft (60 ft Ø at 33 ft)
  • Link each aisle's sensors to that aisle's controller only
  • Controllers act as repeaters for long buildings
QtyModelDescription
6E9T-OSHSelf-powered high bay occupancy sensor, two per aisle
3E9X-DUV-10VTP20 A 0-10V dimming controller, one per aisle

Tech sheet: ES-TS-105 / 107

C

Solution C: Sensor in every fixture

Fixture-integrated · private label
Aisle 1Aisle 2Aisle 3
  • Fixture with sensor module
  • Racking
  • Aisle (own control group)

An ISI MOD17M module in each high bay fixture controls that fixture, so the lit area follows the lift down the aisle. See ES-DG-06 for fixture-integrated design.

  • One module per fixture; long-range optic for high mounting
  • Modules with the same output can be wired in parallel
  • Specify modules with the fixture order for factory install
QtyModelDescription
15ISI-MOD17M10V12VLuminaire sensor module, one per fixture
1512 V DC supplyISI-PSU12VDC or driver auxiliary supply

Tech sheet: ES-TS-104

Design tips

Related tech sheets

ES-TS-104 ISI smart sensors · ES-TS-105 Self-powered wireless sensors · ES-TS-107 Wireless load controllers

Download this guide as a PDF. Other guides: Private offices · Open offices & classrooms · Restrooms & stalled spaces · Hotels & dorms · Fixture-integrated sensing

Starting points only: check every project against its adopted energy code, the reflected ceiling plan and current manufacturer data. Diagrams are illustrative. Send plans to info@energiocontrols.com for a project layout. Products by B.E.G., DANLERS and ILLUMRA. Photo: Unsplash License.