← Energio SensorsDownload PDF
Application design guideES-DG-01Rev B · November 2026

Private offices

Vacancy (manual-on) control for single-occupant rooms

Design guide
Private offices
Photo: Alex Tyson / Unsplash

A private office is the simplest room on the drawings and the one codes look at most closely: the lights must go off on their own when the room empties, and they may not come on to full power by themselves. Three Energio Sensors solutions cover new construction, rooms where the switch location doesn't work, and retrofits with no new wire.

Design goals

Solutions in this guide

Code checklist

RequirementTypical code targetHow the solutions meet it
Automatic shutoffOff within 20 minutes of vacancySensor time-out set to 20 min or less
Restricted auto-onManual-on, or auto-on to no more than 50% of lighting powerVacancy mode on every solution
Local manual controlA manual control in the roomWAVE button, low-voltage switch or battery-free rocker
Automatic receptacle control50% of receptacles in private offices off within 20 min (ASHRAE 90.1)Second relay (WAVE DR) or PP-A-J auxiliary relay

Typical requirements of ASHRAE 90.1-2019 and the 2021 IECC. Local amendments and other code editions differ; the adopted code for the project governs.

A

Solution A: Wall switch sensor

Line voltage · new or existing box
DeskWAVE
  • Wall switch sensor and pattern
  • Light fixture
  • Door

One device replaces the light switch. The occupant presses the WAVE button to turn the lights on; the PIR turns them off after the room empties.

  • Mount on the latch side of the door so it looks into the room
  • Choose the -V model for vacancy-only operation
  • Use the -DR dual-relay model for bi-level or a switched receptacle
QtyModelDescription
1WAVE-PIR-V-120/277-NVacancy-only PIR wall switch sensor
1Wall plateDecorator plate

Tech sheet: ES-TS-103

B

Solution B: Ceiling sensor + power pack

Low voltage · L-shaped or blocked rooms
DeskPLV switch
  • Ceiling sensor and pattern
  • PPower pack (above ceiling)
  • Low-voltage switch

A MINI ceiling sensor sees the whole desk area even when furniture blocks the view from the door. A low-voltage momentary switch gives manual-on; the power pack switches the load.

  • Center the MINI over the work area, 13 ft Ø seated coverage
  • Set the PP-A-J mode switch to manual (vacancy)
  • Aux relay can drop a receptacle circuit or signal HVAC
QtyModelDescription
1MINI-P-PP-A-FC-IP20Primary ceiling sensor, switching
1PP-A-J-120-277VPower pack with aux relay
1LV momentary switchManual on/off at the door

Tech sheet: ES-TS-101 / 102

C

Solution C: Battery-free wireless retrofit

No new wire · occupied buildings
DeskSC
  • Ceiling sensor and pattern
  • SBattery-free rocker
  • CArea controller

A self-powered ceiling sensor and a stick-on rocker talk to an area controller at the fixture. Nothing to fish through finished walls and no batteries to replace.

  • Mount the E9T-OSC at 7–10 ft; it covers 34 ft Ø
  • Stick the rocker where the switch belongs
  • Land the controller in the fixture or a nearby box; set it to vacancy
QtyModelDescription
1E9T-OSCSelf-powered ceiling occupancy sensor
1E9T-S1ABattery-free rocker switch
1E9X-RUV-4IBTP20 A on/off area controller

Tech sheet: ES-TS-105 / 106 / 107

Design tips

Related tech sheets

ES-TS-103 WAVE wall switch sensors · ES-TS-101 MINI ceiling & fixture sensors · ES-TS-102 Power packs · ES-TS-105 Self-powered wireless sensors · ES-TS-106 Wireless switches & keypads · ES-TS-107 Wireless load controllers

Download this guide as a PDF. Other guides: Open offices & classrooms · Warehouses & high bay · Restrooms & stalled spaces · Hotels & dorms · Fixture-integrated sensing

Starting points only: check every project against its adopted energy code, the reflected ceiling plan and current manufacturer data. Diagrams are illustrative. Send plans to info@energiocontrols.com for a project layout. Products by B.E.G., DANLERS and ILLUMRA. Photo: Unsplash License.