Vacancy (manual-on) control for single-occupant rooms

A private office is the simplest room on the drawings and the one codes look at most closely: the lights must go off on their own when the room empties, and they may not come on to full power by themselves. Three Energio Sensors solutions cover new construction, rooms where the switch location doesn't work, and retrofits with no new wire.
| Requirement | Typical code target | How the solutions meet it |
|---|---|---|
| Automatic shutoff | Off within 20 minutes of vacancy | Sensor time-out set to 20 min or less |
| Restricted auto-on | Manual-on, or auto-on to no more than 50% of lighting power | Vacancy mode on every solution |
| Local manual control | A manual control in the room | WAVE button, low-voltage switch or battery-free rocker |
| Automatic receptacle control | 50% of receptacles in private offices off within 20 min (ASHRAE 90.1) | Second relay (WAVE DR) or PP-A-J auxiliary relay |
Typical requirements of ASHRAE 90.1-2019 and the 2021 IECC. Local amendments and other code editions differ; the adopted code for the project governs.
One device replaces the light switch. The occupant presses the WAVE button to turn the lights on; the PIR turns them off after the room empties.
| Qty | Model | Description |
|---|---|---|
| 1 | WAVE-PIR-V-120/277-N | Vacancy-only PIR wall switch sensor |
| 1 | Wall plate | Decorator plate |
Tech sheet: ES-TS-103
A MINI ceiling sensor sees the whole desk area even when furniture blocks the view from the door. A low-voltage momentary switch gives manual-on; the power pack switches the load.
| Qty | Model | Description |
|---|---|---|
| 1 | MINI-P-PP-A-FC-IP20 | Primary ceiling sensor, switching |
| 1 | PP-A-J-120-277V | Power pack with aux relay |
| 1 | LV momentary switch | Manual on/off at the door |
Tech sheet: ES-TS-101 / 102
A self-powered ceiling sensor and a stick-on rocker talk to an area controller at the fixture. Nothing to fish through finished walls and no batteries to replace.
| Qty | Model | Description |
|---|---|---|
| 1 | E9T-OSC | Self-powered ceiling occupancy sensor |
| 1 | E9T-S1A | Battery-free rocker switch |
| 1 | E9X-RUV-4IBTP | 20 A on/off area controller |
Tech sheet: ES-TS-105 / 106 / 107
ES-TS-103 WAVE wall switch sensors · ES-TS-101 MINI ceiling & fixture sensors · ES-TS-102 Power packs · ES-TS-105 Self-powered wireless sensors · ES-TS-106 Wireless switches & keypads · ES-TS-107 Wireless load controllers
Download this guide as a PDF. Other guides: Open offices & classrooms · Warehouses & high bay · Restrooms & stalled spaces · Hotels & dorms · Fixture-integrated sensing
Starting points only: check every project against its adopted energy code, the reflected ceiling plan and current manufacturer data. Diagrams are illustrative. Send plans to info@energiocontrols.com for a project layout. Products by B.E.G., DANLERS and ILLUMRA. Photo: Unsplash License.