Restrooms & stalled spaces

Sensing that keeps the lights on for people behind partitions

Design guide
Restrooms & stalled spaces
Photo: jacopo marello / Unsplash

A PIR sensor needs line of sight, and a restroom stall takes it away. In multi-stall rooms, dual technology adds ultrasonic sensing that fills the room and detects motion behind partitions. Single-user restrooms are simpler: the occupant is always in view.

Design goals

Solutions in this guide

Code checklist

RequirementTypical code targetHow the solutions meet it
Automatic shutoffOff within 20 minutes of vacancyTime-out 20 min or less
Auto-onFull automatic-on is permitted in restroomsOccupancy (auto-on) mode
Local manual controlA manual control in the spaceWAVE push-button or battery-free rocker
Egress / emergencyEmergency lighting stays on as requiredKeep emergency circuits off the sensor, or use a listed transfer device

Typical requirements of ASHRAE 90.1-2019 and the 2021 IECC. Local amendments and other code editions differ; the adopted code for the project governs.

A

Solution A: Multi-stall: dual-technology wall sensor

Line voltage · PIR + ultrasonic
StallStallStallLavsWAVE-DT
  • Wall switch sensor and pattern
  • Ultrasonic coverage (dual technology)
  • Door

The WAVE-DT replaces the entry switch. PIR catches people walking in; ultrasonic fills the room and keeps the lights on for people inside stalls.

  • Mount at the entry with a clear view toward the stalls
  • Adjust ultrasonic sensitivity so the door swing alone doesn't hold the lights
  • Large or L-shaped rooms: send the plan to Energio for a layout
QtyModelDescription
1WAVE-DT-120/277-NDual-technology wall switch sensor
1Wall plateDecorator plate

Tech sheet: ES-TS-103

B

Solution B: Single-user restroom: wall sensor

Line voltage · PIR
WCLavWAVE
  • Wall switch sensor and pattern
  • Door

In a single-user room the occupant is always in view, so a PIR WAVE in occupancy mode turns the lights on at entry and off after the room empties.

  • Mount at the latch side of the door, inside the room
  • Set occupancy (auto-on) mode and a short time-out
  • Pair the exhaust fan on the second relay with the DR model
QtyModelDescription
1WAVE-PIR-120/277PIR wall switch sensor
1Wall plateDecorator plate

Tech sheet: ES-TS-103

C

Solution C: Single-user retrofit: battery-free

No new wire
WCLavSC
  • Ceiling sensor and pattern
  • SBattery-free rocker
  • CArea controller

Where there's no neutral or the switch box can't take a sensor, a self-powered ceiling sensor links to a controller at the fixture; a stick-on rocker gives manual off.

  • Center the E9T-OSC on the ceiling (34 ft Ø at 7–10 ft)
  • Set the controller to occupancy (auto-on)
  • In low light, fit the sensor's backup battery
QtyModelDescription
1E9T-OSCSelf-powered ceiling occupancy sensor
1E9X-RUV-4IBTP20 A on/off area controller
1E9T-S1ABattery-free rocker

Tech sheet: ES-TS-105 / 106 / 107

Design tips

Related tech sheets

ES-TS-103 WAVE wall switch sensors · ES-TS-105 Self-powered wireless sensors · ES-TS-106 Wireless switches & keypads · ES-TS-107 Wireless load controllers

Download this guide as a PDF. Other guides: Private offices · Open offices & classrooms · Warehouses & high bay · Hotels & dorms · Fixture-integrated sensing

Starting points only: check every project against its adopted energy code, the reflected ceiling plan and current manufacturer data. Diagrams are illustrative. Send plans to info@energiocontrols.com for a project layout. Products by B.E.G., DANLERS and ILLUMRA. Photo: Unsplash License.