Zoned occupancy control with daylight harvesting at the windows

Large rooms have two problems a single sensor can't solve: people sit still for long stretches, and the windows supply much of the light for part of the day. Each solution below splits the room into zones no larger than 600 ft², gives every zone its own occupancy control, and dims the window zone to the daylight.
| Requirement | Typical code target | How the solutions meet it |
|---|---|---|
| Control zones | Open plan offices: zones of no more than 600 ft² (IECC) | One control group per zone in every solution |
| Shutoff / partial-off | Off, or reduced by at least 80% (IECC) / 50% (90.1), within 20 min of the zone emptying | Time-out 20 min or less; unoccupied level set per zone |
| Restricted auto-on | Manual-on or auto-on to no more than 50% | Manual switch per zone, or auto-on to a reduced level |
| Daylight-responsive control | Continuous dimming in primary sidelighted zones | Daylight sensor in the window zone drives 0-10V / 1–10 V dimming |
Typical requirements of ASHRAE 90.1-2019 and the 2021 IECC. Local amendments and other code editions differ; the adopted code for the project governs.
Each zone gets a primary MINI with a daylight sensor on its own PP-DIM-J, plus secondary MINIs to extend seated coverage. A low-voltage switch per zone gives manual control.
| Qty | Model | Description |
|---|---|---|
| 2 | MINI-P-PP-DIM-FC | Primary with daylight sensor, one per zone |
| 6 | MINI-S-PP-FC-IP20 | Secondary sensors, three per zone |
| 2 | PP-DIM-J-120-277V | Dimming power pack, one per zone |
| 2 | LV momentary switch | Manual control per zone |
Tech sheet: ES-TS-101 / 102
DANLERS ISI ceiling sensors have a built-in photocell and 0-10V output, so each sensor dims its own fixture group. Time-out, levels and daylight targets are set from the ISI app.
| Qty | Model | Description |
|---|---|---|
| 6 | ISI-CEFL10V12V | Ceiling flush sensor with photocell, 0-10V, three per zone |
| 2 | ISI-PSU12VDC | 12 V DC supply, one per zone |
| — | 0-10V control wiring | Sensor to drivers, per zone |
Tech sheet: ES-TS-104
Self-powered ILLUMRA occupancy sensors and a light sensor link to one dimming controller per zone. Stick-on rockers give manual control without opening walls.
| Qty | Model | Description |
|---|---|---|
| 4 | E9T-OSC | Self-powered ceiling occupancy sensors |
| 1 | E9T-OBP | Wireless PIR and light sensor, window zone |
| 2 | E9X-DUV-10VTP | 20 A 0-10V dimming controller, one per zone |
| 2 | E9T-S1A | Battery-free rockers |
Tech sheet: ES-TS-105 / 106 / 107
ES-TS-101 MINI ceiling & fixture sensors · ES-TS-102 Power packs · ES-TS-104 ISI smart sensors · ES-TS-105 Self-powered wireless sensors · ES-TS-106 Wireless switches & keypads · ES-TS-107 Wireless load controllers
Download this guide as a PDF. Other guides: Private offices · Warehouses & high bay · Restrooms & stalled spaces · Hotels & dorms · Fixture-integrated sensing
Starting points only: check every project against its adopted energy code, the reflected ceiling plan and current manufacturer data. Diagrams are illustrative. Send plans to info@energiocontrols.com for a project layout. Products by B.E.G., DANLERS and ILLUMRA. Photo: Unsplash License.